Case Studies · Healthcare

Healthcare

  • Industry: Healthcare
  • Location: Florida
  • Stats: PRESSURE DROP: 74%, PROJECT SIZE: 1 AHU, COIL DEPTH:12"
Healthcare case study image

Equipment

Unit nameUnit sizeCoil depthPre-readPost-readReduction
AHU-120,000 CFM
50 Tons
12″7.011.8274%

Assumptions

Electricity cost/kWh$0.14
Operating days/week7
Operating hours/day24

What was done

After performing coil cleaning and penetrating through the full depth of the coil:

  • Average pressure across all units dropped by 74%
  • Fan energy savings of 166,249 kWh

Pressure drop

Pre-Read7.01 In-Wg
Post-Read1.82 In-Wg

Annual savings

$24,893Total cost savings
$1,618Cooling savings
$23,275Fan savings
116 MTCO2 emissions removed

Pre-Read & Post-Read

Pre-read meter reading
Pre-read
Post-read meter reading
Post-read